2.13.1.3 Check that the end of the tube is free from burrs and sharp edges or damage will occur to the O-Ring in the push-fit fitting. |
2.13.1.4 Allow 27mm of pipe for insertion into the fitting plus 10mm of pipe to allow use of a disconnecting tool. |
2.13.1.5 Insert the tube through the release collar of the fitting to rest against the grab ring. |
2.13.1.6 Push the tube in firmly until it reaches the tube stop with a positive 'click'. |
3 COLD MAINS SUPPLY. |
3.1 The Cold Mains supply should not exceed 5 bar pressure, or a flow rate of 30 litres per minute. |
3.2 IMPORTANT: A Mains Isolating Valve must be fitted onto the incoming mains within the cylinder cupboard within clear view of the house-holder. |
3.3 IMPORTANT: A Y-Pattern Strainer (supplied loose) must be fitted onto the incoming mains. The Y-Pattern Strainer should be fitted down-flow of the Isolating Valve in a position to enable servicing. |
3.4 In areas of hard water it is recommended that a In-Line Scale Inhibitor be fitted on the incoming mains supply, and installed as per manufacturers instructions. |
3.5 In areas where hard water is known to be a problem, it is recommended that an Electronic Scale Inhibitor be fitted on the incoming mains supply. Details available upon request |
4 CONNECTIONS TO Heat Bank Thermal Store. |
4.1 Cold Mains In. |
4.2 Hot Water Out. |
4.3 Flow from Boiler. |
4.4 Return to Boiler |
4.5 Flow to Heating Circuit |
4.6 Overflow, 22mm Copper IMPORTANT: PLASTIC PIPE SHOULD NOT BE USED. |
4.7 Primary Pressure Relief, should be fitted to provide a visible warning of discharge. |
5 WIRING |
5.1 All cable should be Heat Resistant, and suitable for 230V 50Hz supply. |